HPL Finish & Colour References
Explore HPL colour references for your raised access floor. Choose a colour below, then discuss a physical sample and its compatibility with your selected panel.
Explore HPL Finished Steel Raised FloorFind your finish.
Click a swatch to include its colour code in your sample enquiry.
Select a colour reference for your enquiry.
Screen colours are indicative. Confirm colour and texture against a physical sample before ordering.
Pair the colour.
Specify the floor.
These swatches are a finish reference for raised access floors. Confirm the colour, finish thickness, panel model and edge detail together.
Colour alone does not establish electrical performance. Confirm the required grade and test documentation for the selected finish and complete floor system.
View HPL raised floor models & performanceHPL facing specifications.
Choose from six marble, mineral and wood-effect HPL facing colours, with thickness and surface requirements selected for your panel configuration.
- Facing thickness options
- 1.2 / 1.6 mm
- Tested specimens
- 600 × 600 × 1.2 mm laminate; 3 specimens
- Test reference
- SJ/T 11236-2020; 7 September 2026; 23.2°C / 51.3% RH
| Facing property | Requirement | Measured results |
|---|---|---|
| Surface resistance | 1.0 × 10⁴–1.0 × 10⁹ Ω | 3.57 / 3.37 / 3.60 × 10⁸ Ω |
| Volume resistance | 1.0 × 10⁴–1.0 × 10⁹ Ω | 1.45 / 1.39 / 1.35 × 10⁸ Ω |
| Surface abrasion | Normal ≥400; high ≥1000; ultra-high ≥3000 revolutions | 3250 revolutions |
| Tensile strength | ≥60 MPa | 74.5 MPa |
Reference: Panelway HPL Facings · p3. Results apply to the tested 600 × 600 × 1.2 mm laminate specimens. Complete-panel performance is specified separately.